2.4 LEAK SENSOR INSTALLATION IN PIPING SUMPS AND DISPENSER PANS
Check the specific design drawings for the job, or use the LS600LD Series as illustrated in Figure
1-5. Install sensor per Figure 2-3 as follows:
1. Measure the "MOUNTING HEIGHT" from conduit or junction box to the bottom of the SUMP (or
MANHOLE, VAULT or DISPENSER PAN).
2. Feed the sensor cable through the watertight CONNECTOR to length suitable for the MOUNTING
HEIGHT; or to allow sensor to rest on the containment bottom; or as required by local codes.
Feed an additional 12 inches past the CONNECTOR for splicing inside the junction box; cable
may be cut to proper length.
3. Thread the CONNECTOR into the WATERTIGHT JUNCTION BOX and tighten the
CONNECTOR cord grip over the cable to insure a WATERTIGHT SEAL. The sensor should rest
on the containment floor or as required by local codes.
4. Complete the wiring installation in accordance with Section 3.
Figure 2-4 - Leak Sensor Installation in Piping Sumps, Manholes, and Dispenser Pans
MOUNTING HEIGHT
SENSOR FLEXIBLE CABLE
LIQUID TIGHT
CABLE GRIP
WATERTIGHT JUNCTION BOX
AND CONDUIT SEAL
LEAK SENSOR
MANHOLE
PIPING SUMP O
R
DISPENSER PAN
DRAWING NO. 20017 REV. D