LC1000 INSTRUCTION MANUAL PRODUCT DESCRIPTION
PAGE 10
1.3 LIQUID SENSOR DESCRIPTION
The LC1000 can be integrated with a variety of liquid sensors used for monitoring in-tank levels
and secondary containment areas around tanks and pipes. The maximum is 4 sensors depending
on the overall job configuration; check the specific job design drawings for the actual number and
type specified. Figures 1-5 through 1-8 show four (4) sensor types provided by Pneumercator with
their most typical applications. Other non-Pneumercator models may be used; however, their use
with the LC1000 should have been approved by Pneumercator and local regulators before
attempting to wire them into the system.
Figure 1-5 – LS600LD Series
Commonly used in Sumps, Dispenser Pans, and Steel Tank Interstitial Spaces
Figure 1-6 – LS610
Commonly used in Dry Interstitial Spaces of Fiberglass Tanks
DRAWING NO. 20006 REV. D
4.00"
[102]
Ø1.50"
[38]
Ø1.75"
[45]
1/2" [13] LIQUID
TRIP POINT
304 STAINLESS
STEEL
BUNA N
FLOAT
NYLON
25' (7.5M) LONG
22AWG [.762 DIA.]
2-CONDUCTOR
CABLE
TEFLON
304 STAINLESS
STEEL
316 STAINLESS
STEEL FLOAT
LS600LDBN-1 LS600LDSS
4.00
[102
1/2" [13] LIQUID
TRIP POINT
DIMENSIONS: INCHES [MM]
DIMENSIONS: FEET (M)
CABLE GRIP
CABLE GRIP
25' (7.5M) LONG
22AWG [.762 DIA.]
2-CONDUCTOR
CABLE
DRAWING NO. 20008 REV. A
.236 [6] REF.
.40" [10]
3.02" [77]
1.50" [38]
Ø.130" [3.3]
PULL HOLE
1/2" [13] LIQUID
TRIP POINT
CABLE GRIP
25' (7.5M) LONG
CABLE
DIMENSIONS: INCHES [MM]
DIMENSIONS: FEET (M)