17
CEC Weight
Efficiency
96.2%
96.4%
96.4%
96.5%
Grid Output
Rated Power
7.5 kW
10 kW
11 kW
12.5 kW
Max. Output
Current (@
240V)
32 A
42 A
45.8 A
52 A
Rated Voltage
120 / 240 Vac Split Phase
Rated
Frequency
60 Hz
Adjustable
Power Factor
0.8 Leading ~ 0.8 Lagging
THD
3%
Max. Output
Overcurrent
Protection
87.5 A
Max. Output
Fault
Current And
Duration
250 A Peak@49.8μs
Synchronization
In-Rush Current
<42 A
Grid /
Generator
Input
Rated Power
7.5 kW
10 kW
11 kW
12.5 kW
Voltage Range
216 Vac ~ 264 Vac
Frequency
Range
55 Hz ~ 65 Hz
Max. Input
Current
32 A
42 A
45.8 A
52 A
100 A Pass Through/Bypass
Max. Input
Short Circuit
Current
87.5 A
250 A Peak Pass Through/Bypass
Load
Output
Rated Power
7.5 kVA
10 kVA
11 kVA
12.5 kVA
Rated Voltage
120 / 240 Vac Split Phase