Automatic boiler for wood pellets
Instructions for installation and operation
5.4 STORAGE OF FUEL
Wood pellets have to be in a dry place protected against atmospheric effects because humidity
damages them and aggravates their burning parameters. Excessive humidity completely destroys pellets.
They should be stored in a different room than the boiler or at least 1,500 mm from the boiler.
Operating stock of fuel may be stored in a special central bin which has to be manufactured from
non-combustible material. Bins supplied by the manufacturer meet operating and safety requirements. They
may be filled without any limits up to their total volume.
Large-volume bins have to meet corresponding fire and safety regulations. The supplier is obliged to work
out working regulations and instructions for operation and maintenance of large-volume bins.
5.5 BOILER ROOM VENTILATION
Permanent ventilation of the boiler within approximately 75 m
3
x hour
-1
of fresh air has to be
ensured, if a boiler of approximately 20 kW of power output is operated.
6 PUTTING THE PRODUCTS INTO OPERATION
6.1 CONNECTING TO THE SYSTEM
Connection to the system is performed in a usual manner - see the below given installation dimensions of
products. Recommended connection of the boiler to the heating system - see figures number 13, 14, 15.
Fi
g
ure number 10 - Installation dimensions of boilers