4. Use
Parameters table
4. Use
N° Description Adjustment range
Factory
setting
Remarks
0
Reserved - Do not adjust 8~37°C 12°C Reserved
1
Default temperature 15~40°C 27°C Adjustable
2
Defrost auto-activation time 10~90 min 40 min Adjustable
3
Defrost activation temperature -30~0°C 0°C Adjustable
4
Defrost deactivation temperature 1~30°C 2°C Adjustable
5
Maximum defrost duration 10~40 min 30 min Adjustable
6
Adjustment of temperature difference for restart 2~10°C 3°C Adjustable
7
Automatic restart
0 = OFF
1 = ON
1 Adjustable
8
Reserved - Do not adjust 0 / 1 / 2 0 Reserved
9
Reserved - Do not adjust 0 / 1 0 Reserved
A
Reserved - Do not adjust 8~60°C 30°C Reserved
B
Antifreeze protection - low air temperature 0~15°C 8°C Ajustable
C
Antifreeze protection - low water temperature 2~14°C 4°C Ajustable
D
Reserved - Do not adjust - - Reserved
E
Reserved - Do not adjust 0 / 1 0 Reserved
F
Reserved - Do not adjust 3~20°C 5°C Reserved
H
Reserved - Do not adjust 5~20°C 13°C Reserved
J
Reserved - Do not adjust 65~90°C 70°C Reserved
o
Water intake temperature -9~99°C Actual data
P
Water outlet temperature -9~99°C Actual data
t
Coil temperature -9~99°C Actual data
U
Ambient air temperature -9~99°C Actual data