INSTALLATION GUIDE
SET-UP PROCEDURES
Perform a setup at the control as follows:
§ Ensure main power is on
§ At the I/O control board, depress the SW1 button for approximately 5 seconds. When the red LED (LD2) at the Adjustment Board
begins flashing rapidly, release the button. The blue LED will continue flashing.
§ Door will slowly go open, recycle partially, close and then re-open.
§ Do not interrupt the process and do not move the door manually during this time.
§ If the door does not open and the red LED (DL2) is flashing slowly, check to make sure the motor is plugged in properly at the control
board. Correct as necessary.
§ Once the setup process is complete, the door will close and the LED will go out.
§ Setup is complete.
IMPORTANT NOTE: If the operator stroke is altered in any way, a re-learn must be accomplished.
§ Upon completion of the Setup, activate the door to open and ensure all performance is acceptable.
§ Adjust opening and closing speed, as necessary. If speeds are changed, a re-learn is not required.
§ A re-learn is not required following a main power recovery.
§ Adjust hold-open time as required.
§ Additional adjustments are available through the TAP.
B1 – Battery – use CR1216 battery – required to
maintain timer settings and date programmed
by the TAP
TR1 – Opening speed adjustment
TR2 – Closing speed adjustment
TR3 – Hold-open time adjustment
TR4 – Closing speed adjustment when power is
OFF TR4 will only be enabled when jumper
J6 is moved to the correct pins. (it is enabled
by default).
J2 – USB port
J4 – Ribbon cable connector between boards
J5 – Motor Connector
J7 – Power supply connector between boards
SW1 – “Parameter Changed” button
SW2 – 10 Position “Functions” Dip Switch
For adjustments beyond those mentioned
herein, use the TAP. See TAP Users Guide
for additional information.
WWW.PORTALP.COM | 24
Automatic Doors & Building Access Control
SW10 (Full Power) & SW19 (Low Energy)