EasyManuals Logo

Power Electronics VS65 Series Programming And Software Manual

Power Electronics VS65 Series
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
POWER ELECTRONICS
VS65 SERIES MV SOFT STARTER
PARAMETERS DESCRIPTION
17
E
N
G
L
I
S
H
Screen &
Default Value
Name /
Description
Range
Function
3 OV/LOAD T=5
G3.3 / Overload
curve
1 to 10
The overload curve determines the response time under overload conditions. There is a non-
linear relation between the overload parameter [G3 OV LOAD] and this parameter, in order to
set the time required for tripping on F4 OVERLOAD. If [3 OV/LOAD T =1] is selected then the
response time for an overload condition is almost immediate, but if [OV/LOAD T=10] then takes
the soft starter trips on F4 OVERLOAD after a time delay.
Setting when a fast response is needed under overload conditions, please select
[OV/LOAD T =1]. When a slow response is needed, select [OV/LOAD T =10]. For normal
operation leave this value as default [OV/LOAD T =5].
The response time for the overload protection can be calculated from the following curve:
4 OVL FAC=100%
G3.4 / Starting
Overload
Factor
100 to 500%
The parameter function is to increase the overload curve during acceleration. Recommended to
start loads with elevated torque momentum. Once the nominal rate is reached, this parameter
deactivates and the overload protection will function as it has been explained in [G3.2] and
[G3.3]. Adjust the default (100%) value for low inertia applications like pumps, fans (Torque = K
x Speed²). Mills, crushers and centrifuges (high inertia moment) will normally require a start with
low starting overload factor (150%) and increase this value until the load accelerates without
tripping on F4 OVERLOAD.
This parameter is set in % [G3.3] Overload Curve.
5 MOTOR PTC=-
G3.5 /
Enable/Disable
PTC motor
option
-
Not used for this soft starter model.
6 UNLOAD=0.0A
G3.6 / Under
load current
(0 a 0.9)·In of
VS65
Underload current determines the current level the motor must not operate below.
Leave the adjustment to 50% of the nominal current of the motor.
Applications: This protection helps to detect mechanical problems such as broken shafts, belts,
when this occurs, the motor will run under no load conditions.
When working with pumps, this protection helps to detect no load pump operation, due to a lack
of water or pump input pipe water position.
7 UNLOAD T=OFF
G3.7 / Under
load delay
0 to 99s,
OFF
This parameter sets the maximum allowable operation time under load conditions before
tripping.
The setting depends on the application, but should be set to trip as soon as a condition occurs.
Applications: Pumps, fans.
8 SHEARPIN=OFF
G3.8 / Shearpin
current
(0.6 to 1.2)·In
of VS65,
OFF
The soft starter will stop immediately when the current drawn by the motor reaches this value
during normal operation. This parameter is off during acceleration or deceleration. The stop
should be done in a controlled way.
Set the current value to stop the VS65.
Application: Oversized electrical motors used for starting, but working under nominal conditions
at running, may only reach the Shearpin current because of mechanical problems locked rotors,
etc.
DT0026B
1.51 3.5 4.5 5 5.5 642.5 32
10
1
10
0
10
2
10
3
10
4
In x
Overload curve = 10
Overload curve= 5
Overload curve= 1

Other manuals for Power Electronics VS65 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Power Electronics VS65 Series and is the answer not in the manual?

Power Electronics VS65 Series Specifications

General IconGeneral
BrandPower Electronics
ModelVS65 Series
CategoryController
LanguageEnglish

Related product manuals