KEVIN KU 第 8 頁 2003/3/4
A
PPENDIX B
. S
PECIFICATIONS
MODEL 325A 425A(P) 525A(P) 625A(P)
Capacity 325VA 425VA 525VA 625VA
Voltage
100V, 110V, 115V, 120V, 220V, 230V
240V +/- 25% at line input
INPUT
Frequency 50 or 60Hz +/- 10% (auto sensing)
Voltage (on battery)
Simulated sine wave as utility input power
+/-5 %.
Frequency
(on battery)
50 or 60Hz +/- 0.5Hz
Voltage Regulation AVR AVR automatically increase output voltage
15% above input voltage if –9% to –25% of
nominal. AVR decrease output voltage 13%
below input voltage if +9% to +25% of
nominal.
OUTPUT
Transfer Time 2/4 milliseconds, including detection
Spike Protection 320 Joules, 2ms
EMI/RFI filter 10db at 0.15MHz, 50 db at 30MHz
Overload
Protection
UPS automatic shutdown if overload over
110% of nominal
at 1 min and 130% at 3
seconds
Unit Input Fuse for overload & short circuit protection
10Base-T Cable Port Network (UTP,RJ-45) compatible jacks
PROTECTION
And
FILTERING
Short Circuit UPS output cut off immediately or input fuse
Protection
Type Sealed, maintenance-free lead acid
Typical
Recharge Time
4 hours (to 90% of full capacity)
BATTERY
Back up Time (minutes)
(PC with 15” monitor)
10-20 15-25 20-30 25-35
Net weight Kg (lbs) 4.7
(10.4)
5.7
(12.6)
6.2
(13.7)
6.2
(13.7)
PHYSICAL
Dimension(mm/inch)
WxDxH
97*260
*135
97*320*135
Battery Back-Up Slow beeping sound (about 0.47Hz)
Battery Low Rapid beeping sound (about 1.824Hz)
ALARM
Overload Continuously beeping sound
INTERFACE RS-232 Interface None Bi-directional communication port
Ambient
operation
3,500 meters max. elevation, 0-95% humidity
non-condensing,
0-40
℃
ENVIRONMENT
Audible Noise <40dBA(1 meter from surface)
©
2002. Aug. 08 Version3.0 All right Reserved.
All trademarks are property of their respective owners. Specifications
subject to change without prior notice.