Battery maintenance
The condition of the batteries is crucial to correct operation of the UPS. The UPS units are
provided with the automatic battery test ABM, which continuously controls the condition of
the battery bank. When the capacity of the battery bank has decreased remarkable, the
SERVICE LED starts blinking and audible alarm is activated.
In addition to the automatic battery test it is recommended that a battery discharge test is done
once or twice per year. This test is recommended to be done together with the preventive
maintenance by manufacturer service personnel. In the parallel for redundancy system it is
possible to do a complete discharge test for one UPS without risking the load. The other UPS
will stay in online mode and supply the full load in case of failure in the tested UPS.
Scrapping the UPS
Before scrapping UPS or its battery cabinet, battery bank and lithium battery on the logic
board must be removed. Due to high energy and high voltage, removal of batteries is
allowed only for authorised service personnel. Local requirements must be followed in
battery recycling or discard.
WARNING!
HAZARDOUS MATERIALS. Batteries may contain HIGH VOLTAGES,
and CAUSTIC, TOXIC and FLAMMABLE substances. Batteries can injure or kill
people and damage equipment if used improperly. DO NOT DISCARD unwanted
batteries or battery material in the public waste disposal system. Follow ALL
applicable, local regulations for storage, handling and disposal of batteries and
battery materials.
10. Warranty
The product is warranted against defects in material and workmanship for a period of 12
months from its original date of purchase.
Fig. 11. Control switches of the parallel module
0DLQWHQDQFHE\SDVVVZLWFK6
0DLQWHQDQFHVZLWFK6
0DLQWHQDQFHVZLWFK6