Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
Installing the UPS System
2.1 Preliminary Installation Information
WARNING:
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
· Refer to Appendix A of this manual for installation drawings and additional
installation notes.
· Dimensions in this manual are in millimeters and inches.
· Do not tilt the cabinets more than 10˚ during installation.
· The conduit landing plates are to be removed to add conduit landing holes as
required. Plate material is 16 gauge steel (0.060 in. thick).
· The cabinets must be installed on a level floor suitable for computer or
electronic equipment.
· If perforated floor tiles are required for ventilation, place them in front of the
UPS. Refer to Table AA in Appendix A for equipment weight and point loading.
· Details about control wiring are provided in each procedure for connecting
options and features. Drawing 164201300---2 and Tables X and Y in Appendix A
identify the control wiring terminations.