EasyManua.ls Logo

Prestige Excellence - Factory Trimax Settings; External Modulating Control

Default Icon
114 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
63
External Modulating Control
Factory Trimax Setting
Note 1: The Installer Reset function will set Prestige Model to Solo. Prestige Model must be changed back
to Excellence in Boiler settings.
Note 2: The Installer & EZ Setup Reset functions will set DHW Demand to switch. Use Domestic Hot
Water EZ Setup to change back to a sensor demand.
HEATING SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
H
eating Operation
E
nabled
Demand Switch & Outdoor Reset
Absolute Max CH Setpoint 188°F [87°C]
CH1 Maximum Setpoint 180°F [82°C]
CH1 Minimum Setpoint 120°F [49°C]
Reset Curve Coldest Day 0°F [-18°C]
Reset Curve Warmest Day 64°F [18°C]
CH2 Circuit Enabled
CH2 Maximum Setpoint 140°F 60°C]
CH2 Minimum Setpoint 80°F [27°C]
Warm Weather Shutdown OFF
Pump Constant Circulation Disabled
CH Post Pump Time 1 minute
Freeze Protection Enabled
Frost Protection Setpoint -22°F [-30°C]
Parallel Shift Value 0°F [0°C]
CH Call Blocking 1 minute
System Pump CH1/CH2
DOMESTIC SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
DHW Operation Enabled
Demand (Note 2) Sensor
Boiler DHW Setpoint 186°F [86°C]
DHW Storage Setpoint 140°F [60°C]
DHW On Differential 6°F [3°C]
DHW Storage Adder 46°F [25°C]
DHW Post Pump Time 1 minute
DHW Priority Timeout OFF
DHW Priority Enabled
DHW Call Blocking 0 minute
DHW to CH Call Blocking 1 minute
Antilegionella Function Disabled
BOILER SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
Prestige Model (Note 1) Excellence
Lockout Temperature 210°F [99°C]
Modbus Address 0=BCST

Table of Contents

Related product manuals