Maximum
RPM
600-4000
Maximum allowed RPM of
Engine. Engine running at speed
above this is treated as over
speeding and a fault
is registered and engine stopped.
1600
Minimum
RPM
600-4000
Minimum allowed RPM of
Engine.running at speed below
this is treated as over speeding
and a fault is registered and
engine Stopped.
1400
RPM
Delay
1-999 Sec
Duration for which engine is
allowed to operated outside the
set RPM limits. If it continues to
operate beyond the limits for
more than the
set time a fault condition is
registered and engine stopped.
5
Pick Up
RPM
80-1000
The engine stalling RPM. This
parameter defines the RPM
above which the engine will not
stall and
hence can be treated as running.
This is used to detect the engine
running condition after crank.
1000
Service
Due Hour
10-999Hrs
Service due warning is generated
after the engine has logged these
many hours.
250
Oil temp
Trip Level
40-250oC
The maximum OIL temperature
up to which the engine is allowed
to operate.
o
95 C
Oil temp
trip delay
1-999Sec
Monitoring time for the Oil temp
level to avoid false tripping of the
engine.
10
U
U
U
Page - 9
Operating Instructions