Sensor
Open
1: Warning
2:Fault
3: Disabled
The action to be taken if the
sensor is found to be open.
Warning
Pulses/Re
volution
1-300
No of pulses, from Magnetic
Pickup unit or W point of
charging alternator, in one
revolution of the engine. This
shall be used to calculate the
RPM.
132
Page - 8
Operating Instructions
Start Stop
Config
1: Separate
keys
2: Only Start
key
This parameter decides as to
how the remote start and stop
shall be done. Option 1:
Separate keys is selected
than a single pulse on remote
start shall the engine and
another pulse on remote stop
shall stop the engine. The
duration of these pulses
shall be more than 200msec.
Option 2: In this option the
engine shall be stated and
kept working till Remote start
is pulled low. As soon as the
pin is released the engine
shall stop. To attempt a new
start cycle, after the engine
fails to start, the remote start
pin must be released for some
time and again pulled low.
* Option 2 should not be
selected if the start and stop
functions are to be executed
from front keys.
Separate
keys
B. Engine/Generator Parameter
All the Engine programmable parameters are listed below along with their
default value and minimum / maximum variation range. Values can be
increased or decreased by pressing up/start and down/stop button
respectively . Next parameter can be selected by pressing next button.

Questions and Answers: