10.0 Response To An Alarm
10.1 Automatic Detection
If a smoke detector or heat detector operates on a zone of the 3100 this is known as an
automatic operation. The 3100 responds by.
• Illuminating the ‘General Fire’ indicator.
• Flashing the relevant zone fire indicator.
• Fast intermittent sounding of the internal buzzer.
• Activating non-disabled alarm outputs (after a delay expiry, if programmed).
• Activating the Global Fire contacts.
• Activating the Fire Link output (if fitted and not disabled).
10.2 Manual Detection
If a Manual Call Point is operated on the zone of a 3100 this is known as manual operation.
The 3100 responds by.
• Illuminating the ‘General Fire’ indicator.
• Illuminating the ‘MCP Fire’ indicator.
• Flashing the relevant zone fire indicator.
• Fast intermittent sounding of the internal buzzer.
• Activating non-disabled alarm outputs (immediately).
• Activating the Global Fire contacts.
• Activating the Fire Link output (if fitted and not disabled).
• Overriding any zone delays that may be programmed.
• Re-sounding the alarms if the zone had previously experienced a silenced
automatic activation.
10.3 Delayed Activation
Please see section 8.0
10.4 Silencing the Alarms
The alarms and internal buzzer may be silenced by pressing ‘Silence Alarms’ when in access
level 2.
10.5 Resetting The 3100 After An Alarm
After the cause of the alarm has been determined (and entered in the log by the authorised
user) the 3100 may be reset if required. When in access level 2 press ‘Silence Alarms’ then
press ‘Reset Panel’. The 3100 will reset any latched detectors on its zone connections.
Manual call points must be reset manually at the local location.
10.6 New Zone Into Alarm
If a new zone goes into alarm or a previously silenced zone (triggered by an automatic
device) has a manual activation, the 3100 will re–activate the alarms and re-sound the
internal buzzer.
10.7 Activating The Alarms Manually
To evacuate the building press ‘ Sound Alarms’ when in access level 2. The alarm outputs will
be activated but the Global Fire Contacts and the Fire Link Interface WILL NOT be activated.