17
93-305-05 Issue 0 © Copyright Protec Fire Detection PLC 2004
12.2 To Disable Alarm Outputs
The 3100 can have alarm circuits 1 and 2 and/or alarm circuits 3 and 4 disabled. When an
alarm circuit is disabled faults and activations on that circuit are inhibited.
1. From access level 1 enter your 5 digit user code 1 3 4 4 2 or turn the key-switch
(depending on the model purchased). The ‘Level 2 Accessed’ indicator will illuminate.
2. Using button 2 scroll to the ‘Alarm Outputs’ indication. Any current alarm disablements
will be displayed on row 1 of the display, on zones 1 and 2. Accept this option by pressing
button 3.
3. The ‘Alarm Outputs’ indicator will flash, showing this option has been accepted.
4. Highlight the alarm circuit pair to be disabled by pressing button 2
Highlight zone 1 indicator on row 2 if alarm circuits 1 and 2 are to be disabled.
Highlight zone 2 indicator on row 2 if alarm circuits 3 and 4 are to be disabled.
5. Press button 1 to show that it is to be disabled / not disabled. The relevant row 1 indicator
will be illuminated if the alarm circuit is disabled.
6. Press button 3 to return to the selection menu.
7. Press button 4 to accept and program the disablement set-up and return to access level
2.
8. The yellow ‘General Disablement’ indicator will be illuminated steady, as will the yellow
‘Alarm Outputs’ indicator.
12.3 To Disable Delays
It is possible for the authorised user to override any delays (zonal or fire link) that may have
been set up when the system was commissioned. The procedure to do this is as follows.
1. From access level 1 enter your 5 digit user code 1 3 4 4 2 or turn the key-switch
(depending on the model purchased). The ‘Level 2 Accessed’ indicator will illuminate.
2. Using button 2 scroll to the ‘Alarm Outputs’ indication. Any current setting in this option
will be displayed on row 1 of the display, on zone 3. Accept this option by pressing button
3.
3. The ‘Alarm Outputs’ indicator will flash, showing this option has been accepted.
4. Select the delay override option by pressing button 2 until the row 2 indicator for zone 3 is
illuminated.
5. Press button 1 to show that delays are to be overridden / not overridden. If delays are
overridden the zone 3 indicator on row 1 will be illuminated.
6. Press button 3 to return to the selection menu.
7. Press button 4 to accept and program the set-up and return to access level 2.
8. The ‘Output Delay’ indicator will be extinguished. All delays (zonal and fire link) are
now overridden.