15
93-305-05 Issue 0 © Copyright Protec Fire Detection PLC 2004
11.0 System Disablements
Various disablements may be programmed into the 3100 by the authorised user.
In some situations it may be advantageous to ‘turn off’ certain functions to suit specific site
conditions.
The 3100 permits the following disablements to be made by the authorised user, at access
level 2.
11.1 Zone Disablements
Fires and faults from the disabled zone are inhibited.
11.2 Alarm Disablements
Activations and faults from the disabled alarm circuit are inhibited.
11.3 Delay Disablement
Any programmed zone or fire link delays are overridden.
Important Note:
Delays may have been programmed into the 3100 for valid reasons. Please refer to the
section on delays and consult the system set-up record (appendix 1) before making
adjustments to this part of the system.
11.4 Fire Link Disablement
Activations and faults on the fire link output are inhibited.
Important Note:
Please refer to the section on the fire link and consult the system set-up record
(appendix 1) before making adjustments to this critical part of the system.