93-305-05 Issue 0 © Copyright Protec Fire Detection PLC 2004
12.4 To Disable the Fire Link
It is possible for the authorised user (at access Level 2) to disable the Fire Link interface (if
fitted). Disabling the interface inhibits Fire Link faults and activations.
1. From access level 1 enter your 5 digit user code 1 3 4 4 2 or turn the key-switch
(depending on the model purchased). The ‘Level 2 Accessed’ indicator will illuminate.
2. Using button 2 scroll to the ‘Alarm Outputs’ indication. If the fire link is disabled the zone 4
indicator on row 1 will be illuminated. Accept this option by pressing button 3.
3. The ‘Alarm Outputs’ indicator will flash, showing this option has been accepted, and any
current settings in this option will be displayed on row 1 of the display, on zone 4.
4. Select the ‘Disable Fire Link’ option by pressing button 2 until the indicator for zone 4 is
illuminated.
5. Press button 1 to show that the fire link is to be disabled / not disabled.
6. Press button 3 to return to the selection menu.
7. Press button 4 to accept and program the set-up and return to access level 2.
8. The ‘Fire Link’ and ‘General Disablement’ indicators will be illuminated.