93-520-20 Issue 3.3 Page 8 of 60 CirrusPro Engineer’s Manual
1.2 Factory defaults
(For Reference)
Detectors as supplied or after restoring to factory defaults have the following settings:
If the node text is invalid, it is set to 'CirrusPRO'
The node number, options and number of pipes aren't changed.
High Security Codes set to 123456
Low Security Codes set to 112233
All pipes are set to latch at pre-alarm.
Airspeed is set to 100%.
Airflow error level is set to 20%.
Alarm text is set to:
Pre alarm
Fire 1
Fire 2
Fire 3
Pipe text is set to:
Pipe 1
Pipe 2
Pipe 3
Pipe 4
External inputs are all set to unused.
Relay outputs are set to:
Pre alarm
Fire 1
Fire 2
Fire 3
Output delays are 0
All gain settings are set to 5
All alarm levels are set to 30,50,70 & 90
1.3 UL and ULC information. Pro100, 200, 200+, 200D, 200D+, 200DSC and
200DSC+
The following information is required to ensure the units compliance with the UL listing for UL 268 &
CAN/ULC-S529-02
Detection Principle: Cloud Chamber
Maximum Protected Area:
Pro 100 10,000 square feet (929.03 square meters)
Pro 200 20000 square feet (1858.06 square meters)
Pro 200+ 20000 square feet (1858.06 square meters)
Pro 200D 20000 square feet (1858.06 square meters)
Pro 200D+ 20000 square feet (1858.06 square meters)
Pro 200DSC 20000 square feet (1858.06 square meters)
Pro 200DSC+ 20000 square feet (1858.06 square meters)