VP Keypad Access Device
21
rev. 7-2017 114A3868.E
Setup Parameters/Functions
Setup parameters in the order displayed by the VP access device
are:
Restore Defaults
*=Yes #=No
This prompt only occurs if the program button is held while
powering the device. Pressing the
* key to select YES will restore
all of the factory defaults. WARNING: This will overwrite all setup
parameters including the setup password.
Setup Menus
*=chng #=next
Identifies how to use the keys: the * key is used to change a
parameter and the
# key is the enter key to move to the next menu.
Current Add: 001
New (1-127):
Polling address used by the controller. Any number from 1 to 127
can be entered. The numbers 0 and 22 cannot be used. Each
device connected to the controller must have a unique address.
Factory default is 1.
* to Change Baud:
9600
The controller communications baud rate. Scroll through the list of
available rates by pressing the * key. Factory default is 9600.