EasyManuals Logo

Pulsar PG10000B Owner's Manual

Pulsar PG10000B
43 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
6
Installation (contd)
Supporting and Mounting
Mount the generator on a concrete slab capable of supporting the weight of the generator. The
slab must extend on all sides beyond the frame by at least one foot. Contact a cement contractor
for slab specifications if necessary. Attach the frame to the concrete slab using 3/8” diameter
expansion anchor bolts (not supplied).
Grounding
NOTE: IT IS RECOMMENDED THAT ONLY A TRAINED AND LICENSED
ELECTRICIAN PERFORM THIS PROCEDURE
Connect a #6 AWG grounding wire (not included) from the ground connector (8) on the generator
to a grounding rod (not included) that has been driven at least 24 inches deep into the earth. The
grounding rod must be an earth-driven copper or brass rod (electrode) which can adequately
ground the generator.
Owners Manual
25

Other manuals for Pulsar PG10000B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar PG10000B and is the answer not in the manual?

Pulsar PG10000B Specifications

General IconGeneral
BrandPulsar
ModelPG10000B
CategoryPortable Generator
LanguageEnglish

Related product manuals