EasyManua.ls Logo

Qualitrol SERVERON TM1 - Monitor Installation; Site Preparation

Default Icon
21 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
810-1902-03 Rev D TM1 Installation Guide
7
Monitor Installation
CAUTION: Do not attempt to install your TM1 On-Line Transformer Monitor until you have read and
fully understand the procedures outlined in this document.
Installation of the TM1 consists of the following:
Site preparation
Mounting the monitor
Wiring the monitor
Bleeding air from the monitor
Configuration
Site Preparation
NOTE: Serveron recommends a minimum size of 1” for the transformer oil supply valve and a minimum of
6” vertical clearance between the valve centerline and the transformer foundation for proper installation space.
Ensure the following prior to mounting the monitor:
An adequate valve location for mounting the TM1 monitor has been identified
Power is present and available at the installation site for the monitor
Transformer is oil-filled
All shipped items have been located
Tools / Materials Required
The following tools are required for installation of the TM1 monitor:
7/16”, ½ and 1 ½” wrenches (or an adjustable wrench)
1/8”, 3/16”and 3/32” Allen keys (3/16” Allen key used for optional Moisture Kit only)
Small flat-blade screw driver
Large flat-blade or Phillips screwdriver
Teflon tape and pipe-thread sealant
Wire strippers/cutters
Container to collect oil during installation
Pipe wrench

Related product manuals