EasyManua.ls Logo

Radian RM-111 - Outputs (Port D Only); Output Accessories

Radian RM-111
97 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RM-111 Operations Manual
Specifi cations
Specifi cations
10
2.6 Outputs (Port D Only)
Type: Open collector with 1000 Ohm pull-up to 5V.
Maximum input current: 100 mA (If using RM-10-01 with serial number below
501000 the maximum number of standards the RM-111
will support is 6. The RM-111 will support more of the
newer generation standards).
Vmax Pull Up: 25 volts - 500mW zener clamp at 33 volts
(14.4mA maximum current)
Typical State: Open
2.7 Output Accessories (Port D Only)
RM-1R Electronic/Mechanical Potential Relay
Mechanical Relay Speci cations
Type: Coin silver dry contact relay
Resistance: .004 ohms typical, .005 ohms maximum
Imax: 5 amps AC RMS
Vmax: 630 volts AC RMS (relay clamped at 680V)
VA max Switch: 125 VA inductive
Operate Time: 8 mS maximum
Release Time: 8 mS maximum
Offset Time: 2 mS maximum
Dielectric Withstand: 2.5kV to any other part of the unit