74-05313-000-G 10/16/97 Page 6 © 1988-1997 Radionics, Inc.
Trailer Character
(Trailer Character) sent at the end of D6500 Mode messages, usually a
14
.
Automation Wait
(Automation Acknowledgment Wait Time) (
0 to 255 seconds
) is normally
7
seconds. If the Automation Acknowledgment message is not received by the end of
this time interval, the D6500 will generate a Computer trouble message and activate
its buzzer.
6500 Header Char
(Header Character) This character is sent in front of every standard D6500 Mode
message (normally 21 characters long) and makes the message 22 characters long.
Input Commands
(Input Commands) (
Yes
or
No
) is usually
No
for Automation systems
communicating in SIA mode and
Yes
for Automation systems communicating in
D6500 mode. See the
D6500 Program Entry Guide
for more information.
Link test
(Link Test) (
Yes
or
No
) is usually
No
to disable/reject Link Tests. Set to
Yes
to
initiate/accept a Link Test to/from the Automation system.
Packet Sep.(/)
This prompt enables the final packet separator (/) (in SIA output mode) when
messages with event modifiers are sent to automation. Usually set to
No
.
Sub Subscriber
This is a programmable, Modem Format only, item that determines whether the
specific access control card or token number identifier (sub user) is additionally sent
to the SIA automation output. Usually set to
No
.
3.3 Other Important MPU Program Options
Operation of the buzzer, the internal printer, the external printer, and the RS-232 output depends on the
configuration of these devices: "Always Off, Primary, Secondary or Always On". Operation also depends on
whether the D6500 is in the Manual or Automatic mode.
Non Certified/
Full Manual
UL Burg/Automatic
(without Computer)
UL Fire/Burg/Automatic
(with Computer)
MPU GLOBAL
Auto Ack
No Yes Yes
Buzz in Auto
Yes Yes Yes
Buzz Alarm
No No No
Busy Second Rpts
Yes Yes Yes
Power Supv Rpts
Yes Yes Yes
MPU LINE CARD SUPERVISION
Line Card
(1 through 8) Yes Yes Yes
MPU Internal and External Printer
Device
Primary Primary Always On
Supervision
Yes Yes Yes
MPU AUTOMATION CONFIG
Device
Always Off Always Off Primary
Supervision
Yes Yes Yes
Output Format
6500 6500 6500
LINE CARD
Line Sniff
Yes Yes Yes
Duration
00 0
Refresh
00 0
Table 1: D6500 PROGRAM ITEMS