D6500 Computer Interface Manual
74-05313-000-G 10/16/97 Page 64 © 1988-1997 Radionics, Inc.
FBI Super Fast
Receiver sends to computer:
D6500 Mode: hFrrlssssssaaaaTZZEsst
SIA Mode: <LF><CRC>F <seq><rec><line>[#aaaa|TZZE]<CR>
Receiver sends to printer:
mm/ddshh:mmsFBIsLxxsACCTsaaaasssssssTZZE
+++sACCTsaaaasstttttttttseeeeeeeesiisnnn
FBI: FBI Super Fast format
Lxx: Line number
Definition of automation output codes:
h: Header
F: FBI Super Fast protocol identifier
rr: Receiver number
l: Line Card number
s: Space
aaaa: Account code
T: Zone type
ZZ: Zone number
E: Event type
t: Trailer
Zone /Event Type Code Table:
Code Number Zone/Event Type
1 Fire
2 Panic
3 Burglary
4 Medical
5 Auxiliary
6 Bypass
7 Inactive
8 Eight
9 Nine
0 Zero
B Opening
C Closing
D Abort
E Restore
F Trouble
Definition of printer output codes:
ii: ZN=Zone - ID=User
nnn: Zone/User number
ttttttttt: Up to 9 character zone type, right justified - FIRE, PANIC, BURGLARY,
MEDICAL, AUXILIARY
eeeeeeeee: Up to 8 character event type, left justified - ALARM, RESTORE,
ABORT, TROUBLE, OPEN, CLOSE, BYPASS, INACTIVE