58 ESP-LX+ & LXi+ Installation, Programming, & Operation Guide
Bring three supply wires from the power source through
the conduit into the high-voltage compartment. Strip the
insulation from the incoming wires to expose about ½"
(1,3cm) of bare wire.
Using a code-approved wire connector, connect the wires
as follows:
On 117-120 VAC models (U.S.), connect the black
supply wire (hot) to the black transformer wire.
On 230 VAC models (international), connect the
brown supply wire (hot) to the brown transformer
wire.
On 117-120 VAC models (U.S.), connect the white supply
wire (neutral) to the white transformer wire.
On 230 VAC models (international), connect the blue
supply wire (neutral) to the blue transformer wire.
On 117-120 VAC models (U.S.), connect the green supply
wire (ground) to the green transformer wire.
On 230 VAC models (international), connect the green-
with-yellow-stripe supply wire (ground) to the green-
with-yellow-stripe transformer wire.