RISK OF EQUIPMENT DAMAGE
This product is designed only for use with 0.33V output current transducers (CTs).
DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.
Failure to follow these instructions can result in overheating and permanent equipment damage.
For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must
control conductive pollution and the possibility of condensation or high humidity. Consider the
enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship
with the environment. Installation category: CAT II or CAT III
Provide a disconnect device to disconnect the meter from the supply source. Place this device in
close proximity to the equipment and within easy reach of the operator, and mark it as the
disconnecting device. The disconnecting device shall meet the relevant requirements of IEC 60947-1
and IEC 60947-3 and shall be suitable for the application. Disconnecting fuse holders can be used in
the USA and Canada. Provide overcurrent protection and disconnecting device for supply conductors
with approved current limiting devices suitable for protecting the wiring.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by
the device may be impaired.
This symbol indicates an electrical shock hazard exists.
Documentation must be consulted where this symbol is used on the product.