EasyManua.ls Logo

Raycus RFL-C3000S - Page 15

Raycus RFL-C3000S
38 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wuhan Raycus Fiber Laser Technologies Co., Ltd.
User Guide of RFL- RFL-C3000S
15
If the product is used in an environment that ambient temperature is between -10
and
0
, we recommend to use 30% alcohol, and replace it every two months.
If the product is used in an environment that ambient temperature is below -10
, please
to use dual-system chillers (with heating function) and ensure uninterrupted operation of
the cooling system.
3) Requirements for output cable cooling system:
Rate of liquid flow: 1.7-2.0 L/min;
Pressure of liquid flow: < 0.6 MPa at the inflow;
Type of liquid exchange junction: SMC MS-5H-6:
Type of tube: outer diameter 6; inner diameter 4;
Direction of cooling liquid: unidirectional; connect the tube with the water-pipe strictly
according to direction shown on the layer of the tube;
Type of liquid: de-ionized water, condensed water, pure water;
PH value of liquid: 5.5 - 9;
Filter is needed for the cooling system, and the size of the solid residual practicals should
be within 100um;
Maximum temperature of liquid: 45
:
Minimum temperature of liquid: greater than the saturated dew-point 5
;
Additive to the liquid: satisfies the requirements of PH value and size of solid residual
practicals as above;
Radius of the bending of the armored pipe: off-work state (i.e. transportation and
reservation): minimum radius of bending 20 cm; in-work state: minimum radius of
bending >= 30 cm;
Long-term vibration < 2 G; Impact action < 10 G.
4) Other requirements for chiller:

Related product manuals