EasyManuals Logo

Raypak B6000 User Manual

Raypak B6000
51 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
LEAD LAG, NIGHT SET BACK
Automatic Lead Lag
*Lead Change Hours
Designated lead boiler will change when remaining hours reaches 0.
Range 0-225 hrs. Default value is 100 hrs.
If set at 0 hours lead will not change.
Hours remaining will automatically total.
Enter the desired number of hours of lead boiler operation before change. Hours re-
maining is automatically calculated. Designated lead boiler will change as soon as
remaining hours run out. Set at 0 hours and lead will not change.
STANDARD
BOILER PARAMETERS LEAD LAG, NIGHT SET BACK
Boiler Parameters
*Pump delay selectable from 0 to 20 *Ignition time sets the duration to monitor
minutes. Range 0-20. Default value 3 mins. Ignition prior to lock out. Range 15-100.
Default value 30 secs.
PUSH SELECT
PUMP DELAY
Enter time desired for boiler pump operation, if one is installed and wired to boiler moni-
tor. If there is no pump or a continuous running pump, ignore.
PUSH SELECT
IGN TIME
Display shows time of monitoring the ignition prior to main flame. Default timing is 30
seconds.
Note: On multiple boilers, a time must be entered for each boiler.
Page 30
Pump Del ay I GN T i me
#X: XX m i n XXX s ec
Lead Change hr s . XXX
Hour s Remai ni ng XXX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Raypak B6000 and is the answer not in the manual?

Raypak B6000 Specifications

General IconGeneral
BrandRaypak
ModelB6000
CategoryController
LanguageEnglish

Related product manuals