Aux Heat On Threshold Range: 3 to 8 degrees Default: 3
Sets the delta from setpoint that stage 3 heating starts.
Aux Heat Off Threshold Range: 0 to 7 degrees Default: 0
Sets the delta from setpoint that stage 3 heating stops.
Stage 3 turns off at setpoint + Delta Stage 3.
Cooling Stage 1 On Threshold Range: 1 to 7 degrees Default: 1
Sets the delta from setpoint that stage 1 cooling starts.
Cooling Stage 1 Off Threshold Range: 0 to 6 degrees Default: 0
Sets the delta from setpoint that stage 1 cooling stops.
Stage 1 turns off at setpoint - Delta Stage 1
Cooling Stage 2 On Threshold Range: 2 to 8 degrees Default: 2
Sets the delta from setpoint that stage 2 cooling starts.
Cooling Stage 2 Off Threshold Range: 0 to 7 degrees Default: 0
Sets the delta from setpoint that stage 2 cooling stops.
Stage 2 turns off at setpoint - Delta Stage 2.
Restore Defaults Range: Yes, No Default: No
Restores all settings to factory defaults.
Press Yes to restore defaults
Press No to exit and not restore defaults
Z-Wave Installation
See the Operating Guide for instructions on installing the thermostat on a Z-Wave network.