Commissioning 5
BAL_SD_R62_EN_2V3_BLA_121-006454377 23 / 30
→ ALARMING
→ General
→ PAutoReset ON Selection to switch automatic reset ON or OFF when
alarm is no longer active
→ TTechAlarmDelay 30 (sec) Delay time to active alarming in case of a technical
alarm
→ TLedIntervall 1 (ds) Traffic lights blinking interval during alarm
→ TMatAlarmDelay 60 (sec) Delay time when alarm is from door drives or faulty
sensor
→ PEntranceFlash 0 Flashing light on the entrance indicates the type of
alarm:
0 = all alarms
1 = intrusion
2 = tailgaiting
3 = technical alarm
4 = sabotage
→ TPubOpenDelayTech 5 (ds) Delay time opening public door in case of technical
alarm
→ TSecOpenDelayTech 5 (ds) Delay time opening secure door in case of technical
alarm
→ Buzzer
→ TTechAlarm 10 (min.) Time between repeating signaling with the buzzer when
technical alarm is still active
→ TOnTime 5 (ds) Time the buzzer is on
→ Public door
→TWrongPos 30 (sec) Delay time alarming public door does not open or close
→ TNotOpNotCl 10 (sec) Delay time alarming while public door is between open
and closed position
→ TForcedOpen 10 (ds) Delay time for alarming when the public door is closed
and is no longer sending an opening impulse to the PLC
→ Secure door
→TwrongPos 30 (sec) Delay time alarming secure door does not open or close
→ TNotOpNotCl 10 (sec) Delay time alarming while secure door is between open
and closed position
→ TForcedOpen 10 (ds) Delay time alarming when the secure door is closed and
is no longer sending an opening impulse to the PLC
→ LIGHT
→ PPowerSave ON Power save mode activated ON or deactivated OFF
→ TPowerSave 30 (min.) Delay time before light is switched off when door is not
used
→ TOffDelay 20 (ds) Delay time to switch off the lights (when changing the
operating mode)