Parameter explanations V2.1_V2.6
2
IRA_B8_EN_2V2_REC_102-020401137 36/ 56
→ TOS DV 1 Turn lock surveillance of door leaf 1 for doors featuring a swiv-
elling leaf (door type
TOS
).
▪ Switch position and door function (
Manual mode
) must
→ TOS DV 2 Turn lock surveillance of door leaf 2 for doors featuring a swiv-
elling leaf (door type
TOS
).
▪ Switch position and door function (
Manual mode
) must
→ AKA button Opening to complete opening width (0V/open -> 24V). The
signal is intended for connecting a button on the outer side of
the door.
→ AKA button reduced Opening to reduced opening width (0V/open -> 24V). The sig-
nal is intended for connecting a button on the outer side of the
door.
→ VRR manually Signal for connecting a rod lock (manual locking).
0V/open = rod lock closed
24V = rod lock open
→ SIA Safety signal of presence detector.
0V/open = active safety
24V = passive safety
▪ The signal prevents a closed door from being opened and
an open door from being closed.
▪ In all other phases the signal is disabled.
▪ If the sensor test is configured, the sensor is tested before
each opening and closing.
→ AUX2_OUT Configurable output signals on FEM0 (terminal 54).
▪ The same signals as for STM are available (see
→ Input/Output → STG → AUX0_OUT
).
▪ If the signal is active, 24 volt DC / 0.2 A is connected to
this output.
▪ Due to the hard-wired signal logic, the output does not
have the same flexibility as the output of the STM. For that
reason it may be impossible to implement all the applica-
tions as requested. For example, the signal
Test Sensors
not be available in the required polarity.
INPUT/OUTPUT --> FEM1
→ FEM type This parameter assigns the configurable input and output sig-
nals of the FEM1 to application-compatible default values.
→ Basic X All input and output signals are deactivated.