Parameter explanations V2.1_V2.6
2
IRA_B8_EN_2V2_REC_102-020401137 37/ 56
→ Interlock Configuration for interlock operation.
It is possible to operate the system with sensors between
the doors or without sensors with interlock sequential con-
trol.
Parameter Default value
Input → AUX10_IN S_AUS
Input → AUX11_IN SEA
Input → AUX12_IN SFS_IN
Output → AUX10_OUT SAA
Output → AUX11_OUT SAMP
Output → AUX12_OUT SFS_OUT
→ Pharmacy Configuration for pharmacy control.
The door is opened and closed by an on/off switch.
The movements occur at reduced speed, as no sensors
are active (triggering and safety).
NSK/SÖK is not active!
Parameter Default value
Input → AUX10_IN APS locking contact
Input → AUX11_IN APS opening
Output → AUX10_OUT APS signal light
→ I/O-Set 1 Set of parameters 1
Parameter Default value
Output → AUX11_OUT Alarm output
Output → AUX12_OUT Open
Output → AUX13_OUT Closed
Output → AUX14_OUT Emergency stop / opening
Output → AUX15_OUT ELS error
Output → AUX16_OUT Battery error
Output → AUX17_OUT Locking error
Output → AUX18_OUT Power failure
Output → AUX19_OUT OM Automatic
Output → AUX1A_OUT Reduced opening
Output → AUX1B_OUT OM Continuously open
Output → AUX1C_OUT BA One-Way
Output → AUX1D_OUT BA Locked