Parameter explanations V2.1_V2.6
2
IRA_B8_EN_2V2_REC_102-020401137 41/ 56
→ Reduced OM The relay is active as long as an operating mode with
reduced
opening width
is activated.
→ Power failure The relay is active as long as there is no mains voltage and
the control unit is operated by battery.
▪ If
Parameter → Drive → Power failure
is configured for
Bat-
tery operation
, the relay remains active until the control unit
changes to sleep mode.
▪ If
Parameter → Drive → Power failure
is configured for
Emergency operation
, the relay only remains active during
the action configured with
Parameter → Emergency opera-
tion battery
. Afterwards the control unit change to sleep
mode and the relay is deactiv
→ Locking error The relay is active as long as a locking or unlocking error has
been detected.
→ Battery error Relay active during a battery error.
▪ Depending on door type the battery might only be tested
once per hour.
Accordingly, it can last up to an hour until a battery defect
→ ELS error Relay active during an ELS error.
→ Emergency stop/open Relay active while connection
Emergency stop
or
Emergency
open
is cut.
→ AKI/AKA time The relay is active while an AKI or AKA triggering signal re-
mains activated.
▪ The time until the output is activated can be adjusted with
Parameter → Miscellaneous → Alarm display → Time acti-
vation
.
→ SÖK/NSK The relay is active while an SÖK or NSK signal is triggered.
→ CAN connection The relay is active as long as there is a problem with the CAN
connection between STM and FEM1.
→ Error RED test The relay is activated.
→ Maintenance is due The relay is activated when 95% of the maintenance target
value is reached.
→ Maintenance time ex-
ceeded
The relay is activated when 105% of the maintenance target
value is reached.
→ Redundancy test The relay is activated while a redundancy test is being carried
out.