OFF TIME DELAY
to Sec
Enter the time value in seconds that the output is delayed from turning off
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
Enter the reset action of the output. See figure for details.
 = Automatic action; This action allows the output to
automatically reset off at the trigger points per the Setpoint Action shown in
Setpoint Output Figures. The “on” output may be manually reset (off)
immediately by the front panel RST button or user input.The output remains
off until the trigger point is crossed again.
 = Latch with immediate reset action; This action latches the output on at
the trigger point per the Setpoint Action shown in Setpoint Output Figures.
Latch means that the output can only be turned off by the front panel RST
button or user input manual reset, or meter power cycle. When the user input
or RST button is activated (momentary action), the corresponding “on” output
is reset immediately and remains off until the trigger point is crossed again.
(Previously latched alarms will be off if power up Display Value is lower than
setpoint value.)
 = Latch with delay reset action; This action latches the output on at the
trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch
means that the output can only be turned off by the front panel RST button or
user input manual reset, or meter power cycle. When the user input or RST
button is activated (momentary action), the meter delays the event until the
corresponding “on” output crosses the trigger off point. (Previously latched
outputs are off if power up Display Value is lower than setpoint value. During
a power cycle, the meter erases a previous  reset if it is not activated at
power up.)
OUTPUT RESET ACTION
 


Setpoint Output Reset Actions
This parameter enables the RST button or user input to reset the output when
the display is reset.
Note: For this parameter to operate, the RST button or User Input being used
must be set to  and the Input value must be displayed. If these conditions
are not met, the output will not reset.


OUTPUT RESET WITH DISPLAY RESET

When , the output is disabled (after a power up) until the trigger point is
crossed. Once the output is on, the output operates normally per the Setpoint
Action and Output Reset Action.


STANDBY OPERATION



ON TIME DELAY
Enter the time value in seconds that the output is delayed from turning on
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
to Sec