EasyManua.ls Logo

red lion PAXLA - Module 4: Setpoint Output Parameters

red lion PAXLA
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-9-
Released 2018-01-19 Drawing No. LP0722
The Security Code determines the programming mode and the
accessibility of programming parameters. This code can be used along
with the Program Mode Lock-out (P-Loc) in the User Input Function
parameter (Module 1).
Two programming modes are available. Full Programming mode
allows all parameters to be viewed and modified. Quick Programming
mode permits only the Setpoint values to be modified, but allows direct
access to these values without having to enter Full Programming mode.
Programming a Security Code other than 0, requires this code to be
entered at the CodE prompt in order to access Full Programming mode.
Depending on the code value, Quick Programming may be accessible
before the CodE prompt appears (see chart).
PROGRAMMING SECURITY CODE
000 to 999
000
CodE
USER INPUT
FUNCTION
USER INPUT
STATE
SECURITY
CODE
MODE WHEN “PAR”
BUTTON IS PRESSED
FULL PROGRAMMING
MODE ACCESS
0
Full Programming Immediate Access
not P-Loc
______
1-99
Quick Programming
After Quick Programming
with correct code entry
at CodE prompt *
100-999
CodE prompt
With correct code entry
at CodE prompt *
0
Programming Lock No Access
Active
1-99
Quick Programming No Access
P-Loc
100-999
CodE prompt
With correct code entry
at CodE prompt *
Not Active 0-999
Full Programming Immediate Access
5.4 Module 4 - setpoInt output paraMeters (4-SPt)
PAR
Pro
Enb-n
Setpoint
Action
Setpoint
Select
Setpoint
Value
Output Reset
Action
Hysteresis
Value
Off Time
Delay
On Time
Delay
Output Reset
W/Display
Reset
SPSEL
4-SPt
Act-n SPt-n HYS-n tON-n tOF-n rSt-n rEn-n
Standby
Operation
Stb-n
Setpoint
Enable
PARAMETER MENU
OUTPUT
STATE
OFF
ON
Hys
SP + Hys
SP
OFF
TRIGGER POINTS
Low Acting (Unbalanced Hys) = LO-Ub
OUTPUT
STATE
OFF
ON
Hys
SP
SP - Hys
OFF
TRIGGER POINTS
High Acting (Unbalanced Hys) = HI-Ub
Enter the setpoint (output) to be programmed. The n in the following
parameters will reflect the chosen setpoint number. After the chosen
setpoint is completely programmed, the display will return to SPSEL.
Repeat steps for each setpoint to be programmed. Select NO to exit the
module.
SETPOINT SELECT
NO
SPSEL
NO SP-1 SP-2
Select YES to enable Setpoint n and access the setup parameters. If
NO is selected, the unit returns to SPSEL and Setpoint n is disabled.
SETPOINT ENABLE
NO
Enb-n
YES NO
Enter the action for the selected setpoint (output). See Setpoint
Output Figures for a visual detail of each action.
SETPOINT ACTION
HI-Ub
Act-n
HI-bL
LO-bL HI-Ub LO-Ub
High Acting, with balanced hysteresis
Low Acting, with balanced hysteresis
High Acting, with unbalanced hysteresis
Low Acting, with unbalanced hysteresis
=
HI-bL
=
LO-bL
=
HI-Ub
=
LO-Ub
OUTPUT
STATE
OFF
ON
Hys
SP + ½Hys
SP
SP - ½Hys
OFF
TRIGGER POINTS
High Acting (Balanced Hys) = HI-bL
OUTPUT
STATE
OFF
ON
Hys
SP + ½Hys
SP
SP - ½Hys
OFF
TRIGGER POINTS
Low Acting (Balanced Hys) = LO-bL
SETPOINT VALUE
Enter the desired setpoint value. The decimal point position for the
setpoint and hysteresis values follow the selection set in Module 1.
-19999 to 99999
001.00
SPt-n
* Entering Code 222 allows access regardless of security code.

Other manuals for red lion PAXLA

Related product manuals