7.3 mOdule 3 - lOCKOuT parameTers (3-LC)
SETPOINT OUTPUT 1
POWER
OUTPUT 2
POWER
CONTROLLER
STATUS
PID
GROUPRAMP RATE
SETPOINT
OUTPUT
POWER
OFFSET
PROPORTIONAL
BAND
INTEGRAL
TIME
DERIVATIVE
TIME
INTEGRATION
DEFAULT
ALARM 1
VALUE
ALARM 2
VALUE
SETPOINT
SELECT
ALARM
RESETVALUE
ALARM 3
AUTO-TUNE
START
CONTROL
MODE
DEVIATION
VALUE
CONTROL
MODE
TRANSFER
ACCESS
CODE
P
P
Programming/model dependent.
PARAMETER MENU
SELECTION DESCRIPTION
dISP
Display: accessible in Display Loop.
PArA
Parameter: accessible in Parameter Loop
HIdE
Hide: accessible in Hidden Loop.
LOC
Locked: not accessible in loops.
dSPr
Display/read: read only in Display Loop, but read/write
in Hidden Loop.
The following parameters can be configured for the selections described
above. See Programming Loops section for a description of loops and
parameters.
PARAMETER SELECTION
FACTORY
SETTING
SP
dISP, PArR, HIdE, LOC, dSPr
dISP
OP1
dISP, PArR, HIdE, LOC, dSPr
PArR
OP2
dISP, PArR, HIdE, LOC, dSPr
PArR
SPrP
dISP, PArR, HIdE, LOC, dSPr
PArR
PId
dISP, PArR, HIdE, LOC, dSPr
PArR
r-S
dISP, PArR, HIdE, LOC, dSPr
dISP
OPOF
PArR, HIdE, LOC
PArR
ProP
PArR, HIdE, LOC
PArR
Intt
PArR, HIdE, LOC
PArR
dErt
PArR, HIdE, LOC
PArR
dInt
PArR, HIdE, LOC
LOC
AL-1
PArR, HIdE, LOC
PArR
AL-2
PArR, HIdE, LOC
PArR
AL-3
PArR, HIdE, LOC
PArR
ALrS
PArR, HIdE, LOC
PArR
SPSL
PArR, HIdE, LOC
PArR
tUNE
HIdE, LOC
HIdE
CtrL
HIdE, LOC
HIdE
trnf
HIdE, LOC
HIdE
dEv
dISP, LOC
dISP
Parameters may not appear in selected loop if not applicable to current
operating mode.
Ex. 1. If At2 = NONE, AL-2 will not be displayed in selected loop.
2. If CtrL = ONOF, PID parameters will not be displayed in selected loop.
0
Full access to Display, Hidden, and
Configuration Loops
-1 to -125
Code necessary to access
Configuration Loop only. *
1 to 125
Code necessary to access Hidden
and Configuration Loops. *
* If PLOC is active, Configuration Loop is not accessible.
C
Shaded parameters are programming/model dependent.