7.4 mOdule 4 - alarm parameTers (4-AL) (OpTiOnal)
ALARM 1
RESET
MODE
ALARM 1
ACTION
ALARM 1
ANNUNCIATOR
ALARM 1
STANDBY
ALARM 2
RESET
MODE
ALARM 2
ACTION
ALARM 2
ANNUNCIATOR
ALARM 2
STANDBY
INPUT FAIL
ALARM 1
ACTION
ALARM 1
VALUE
ALARM 2
VALUE
P
P
CHANGE
DISPLAY
COLOR
ALARM 3
VALUE
ALARM
HYSTERESIS
INPUT FAIL
ALARM 3
ACTION
ALARM 3
STANDBY
ALARM 3
ACTION
ALARM 3
RESET
MODE
ALARM 3
ANNUNCIATOR
INPUT FAIL
ALARM 2
ACTION
Programming/model dependent.
PARAMETER MENU
OFF
ON
AL + ½Hys
AL
AL - ½Hys
OFF
Absolute High Acting (Balanced Hys)
Hys
TRIGGER POINTS
ALARM
STATE
ALARM
STATE
OFF ON
Hys
SP + AL
SP
OFF
TRIGGER POINTS
Deviation High Acting (AL > 0)
ALARM
STATE
Hys
SP - AL
SP
SP + AL
Hys
TRIGGER POINTS
ON OFF OFFON ON
Band Inside Acting
OFF ON
AL + ½Hys
AL
AL - ½Hys
OFF
Absolute Low Acting (Balanced Hys)
TRIGGER POINTS
Hys
ALARM
STATE
ALARM
STATE
OFFON
Hys
SP - AL
SP
OFF
TRIGGER POINTS
Deviation Low Acting (AL > 0)
ALARM
STATE
OFF ON
Hys
AL
AL - Hys
OFF
TRIGGER POINTS
Absolute High Acting (Unbalanced Hys)
ALARM
STATE
OFF ON
Hys
AL + Hys
AL
OFF
TRIGGER POINTS
Absolute Low Acting (Unbalanced Hys)
ALARM
STATE
ON OFF
Hys
SP + (-AL)
SP
ON
TRIGGER POINTS
Deviation High Acting (AL< 0)
ALARM
STATE
ON
Hys
SP - AL
SP
OFF
SP + AL
ON
Hys
OFF OFF
TRIGGER POINTS
Band Outside Acting
ALARM ACTION FIGURES
Note: Hys in the above figures refers to the Alarm Hysteresis.
AVAILABLE ALARM ACTIONS
NONE
None
No action, the remaining Alarm
parameters are not available.
AbHI
Absolute High
(balanced hysteresis)
The alarm energizes when the Process
Value exceeds the alarm value + 1/2 the
hysteresis value.
AbLO
Absolute Low
(balanced hysteresis)
The alarm energizes when the Process
Value falls below the alarm value -1/2 the
hysteresis value.
AuHI
Absolute High
(unbalanced hysteresis)
The alarm energizes when the Process
Value exceeds the alarm value.
AuLO
Absolute Low
(unbalanced hysteresis)
The alarm energizes when the Process
Value falls below the alarm value.
d-HI
Deviation High The alarm value tracks the Setpoint value
d-LO
Deviation Low The alarm value tracks the Setpoint value
b-IN
Band Acting (inside) The alarm value tracks the Setpoint value
b-ot
Band Acting (outside) The alarm value tracks the Setpoint value
AbHI - Absolute High Acting (Balanced Hys)
AbLO - Absolute Low Acting (Balanced Hys)
AuHI - Absolute High Acting (Unbalanced Hys)
AuLO - Absolute Low Acting (Unbalanced Hys)
d-HI - Deviation High Acting (AL>0)
d-HI - Deviation High Acting (AL<0) b-ot - Band Outside Acting
b-IN - Inside Acting
d-LO - Deviation Low Acting (AL>0)