31
REGISTER
(4x)
REGISTER NAME LOW LIMIT HIGH LIMIT
FACTORY
SETTING
ACCESS COMMENTS
96 Deadband/Overlap
-99(.9) or
-999 (process)
999(.9)° or
9999 (process)
2 Read/Write
1 = 1 Display unit; In combination Reverse(r) and
Direct(d) modes, this defines the overlap area in
which both OP1 and OP2 are active
(negative value) or the deadband area (positive
value).
97 On/Off Control Hysteresis 2
250(.0)° or 2500
(process)
2 Read/Write 1 = 1 Display unit
LOCKOUT PARAMETERS
101 Setpoint Access 0 4 0 Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
102 Output 1 Power Access 0 4 1 Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
103 Output 2 Power Access 0 4 1 Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
104 Setpoint Ramp Rate Access 0 4 1 Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
105 PID Group Access 0 4 1 Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
106 Controller Status (Run/Stop) Access 0 4 0 Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
107 Output Power Offset Access 1 3 1 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
108 Proportional band Access 1 3 1 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
109 Integral time Access 1 3 1 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
110 Derivative time Access 1 3 1 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
111 Integration Default Access 1 3 3 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
112 Alarm 1 Value Access 1 3 1 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
113 Alarm 2 Value Access 1 3 1 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
114 Alarm 3 Value Access 1 3 1 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
115 Alarm Reset Access 1 3 1 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
116 Setpoint Select Access 1 3 1 Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
117 Auto-Tune Start Access 2 3 2 Read/Write 2 = HIdE, 3 = LOC
118 Auto Control Mode Access 2 3 2 Read/Write 2 = HIdE, 3 = LOC
119 Control Mode Transfer Access 2 3 2 Read/Write 2 = HIdE, 3 = LOC
120 Deviation Value Access 0 3 0 Read/Write 0 = dISP, 3 = LOC
121 Access Code -125 125 0 Read/Write
0 = Full access to display, parameter, hidden, and
configuration loops; -1 to -125 = Code necessary to
access configuration loop only; 1 to 125 = Code
necessary to access hidden and configuration loops
ALARM PARAMETERS
131 Alarm 1 Action 0 18 0 Read/Write
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
132 Alarm 1 Annunciator 0 1 0 Read/Write 0 = Normal, 1 = Reverse
133 Alarm 1 Reset Mode 0 1 0 Read/Write 0 = Automatic, 1 = Latched
134 Alarm 1 Standby 0 1 0 Read/Write 0 = No, 1 = Yes
135 Alarm 1 Value -999 9999 100 Read/Write 1 = 1 Display unit
136 Input Fail Alarm 1 Action 0 1 0 Read/Write 0 = Off; 1 = On
137 Alarm 2 Action 0 18 0 Read/Write
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
138 Alarm 2 Annunciator 0 1 0 Read/Write 0 = Normal, 1 = Reverse
139 Alarm 2 Reset Mode 0 1 0 Read/Write 0 = Automatic, 1 = Latched
140 Alarm 2 Standby 0 1 0 Read/Write 0 = No, 1 = Yes
141 Alarm 2 Value -999 9999 200 Read/Write 1 = 1 Display unit
142 Input Fail Alarm 2 Action 0 1 0 Read/Write 0 = Off; 1 = On
143 Alarm 3 Action 0 18 0 Read/Write
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
144 Alarm 3 Annunciator 0 1 0 Read/Write 0 = Normal, 1 = Reverse
145 Alarm 3 Reset Mode 0 1 0 Read/Write 0 = Automatic, 1 = Latched
146 Alarm 3 Standby 0 1 0 Read/Write 0 = No, 1 = Yes
147 Alarm 3 Value -999 9999 300 Read/Write 1 = 1 Display unit