32
REGISTER
(4x)
REGISTER NAME LOW LIMIT HIGH LIMIT
FACTORY
SETTING
ACCESS COMMENTS
148 Input Fail Alarm 3 Action 0 1 0 Read/Write 0 = Off; 1 = On
149 Alarm Hysteresis 0
250(.0)° or
2500 (process)
0 Read/Write
1 = 1 Display unit; The same value applies to all
alarms.
150 Change Color Intensity 0 4 0 Read/Write
0 = OFF, 1 = Any Alarm, 2 = AL-1, 3 = AL-2,
4 = AL-3
SERIAL COMMUNICATION PARAMETERS
211 Communications Type 0 1 1 Read/Write 0 = ASCII, 1 = rtU
212 Baud Rate 0 4 4 Read/Write 0 = 2400, 1 = 4800, 2 = 9600, 3 = 19200, 4 = 38400
213 Data Bit 7 8 1 Read/Write 0 = 7,1 = 8
214 Parity Bit 0 2 0 Read/Write 0 = No, 1 = Even, 2 = Odd
215 Unit Address 1 247 247 Read/Write
216 Load Serial Settings 0 1 0 Write *
0 = No change, 1 = Load Serial Settings; * - will
read 0
SLAVE ID
1001 N/A N/A
0x524C
(“RL”)
Read Only 0x524C (“RL”)
1002 N/A N/A
0x432D
(“C-”)
Read Only 0x432D (“C-”)
1003 N/A N/A
0x5058
(“PX”)
Read Only 0x5058 (“PX”)
1004 N/A N/A
model
dependent
Read Only
0x55<n> (“Un”) ‘n’ - 1st output;
‘0’(0x30) = No Card installed,
‘x’ (0x78) = any output option card installed
1005 N/A N/A
model
dependent
Read Only
0x<b><c>
<b>(2nd Output): ‘0’ (0x30) = No Card installed,
‘x’ (0x78) = any output option card installed
<c>(Options): ‘9’ = RS485/No User Inputs,
‘A’ = RS485/2 User Inputs
1006 N/A N/A
0x2020
(“ “)
Read Only 0x2020 (“ “)
1007 N/A N/A Read Only
0x0100 = Software database version number in
BCD (0x0100 = 1.00)
1008 N/A N/A 0x10 Read Only 0x10 = 16 reads
1009 N/A N/A 0x10 Read Only 0x10 = 16 writes
1010 N/A N/A 0 Read Only