MI8O2
QUICK INSTALLATION GUIDE
REER S.p.A. Via Carcano 32, 10153 Torino Italia 2
Tel. +39 0112482215 r.a. Fax +39 011859867
Sito web: www.reersafety.com - email: info@reer.it
C) MORSETTIERE - TERMINAL BLOCKS - BORNIERS - ANSCHLUSSKLEMMEN - TERMINALES
PIN
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
(see following table)
Input ("type B" according to EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" according to EN 61131-2)
4
0VDC
-
0VDC power supply
5
OSSD1_A
Output
Static output 1
PNP active high
6
OSSD1_B
Output
PNP active high
7
RESTART_FBK1
Input
Feedback/Restart 1
Input according to EN 61131-2
8
OUT_STATUS1
Output
SIL 1/PL c output
PNP active high
9
OSSD2_A
Output
Static output 2
PNP active high
10
OSSD2_B
Output
PNP active high
11
RESTART_FBK2
Input
Feedback/Restart 2
Input according to EN 61131-2
12
OUT_STATUS2
Output
SIL 1/PL c output
PNP active high
13
OUT_TEST1
Output
Short circuit detection output
PNP active high
14
OUT_TEST2
Output
Short circuit detection output
PNP active high
15
OUT_TEST3
Output
Short circuit detection output
PNP active high
16
OUT_TEST4
Output
Short circuit detection output
PNP active high
17
INPUT1
Input
Digital input 1
Input according to EN 61131-2
18
INPUT2
Input
Digital input 2
Input according to EN 61131-2
19
INPUT3
Input
Digital input 3
Input according to EN 61131-2
20
INPUT4
Input
Digital input 4
Input according to EN 61131-2
21
INPUT5
Input
Digital input 5
Input according to EN 61131-2
22
INPUT6
Input
Digital input 6
Input according to EN 61131-2
23
INPUT7
Input
Digital input 7
Input according to EN 61131-2
24
INPUT8
Input
Digital input 8
Input according to EN 61131-2
CONFIGURATION NODE SEL
NODE_SEL0 (PIN 2)
NODE_SEL1 (PIN 3)
NODE 0
0 (or not connected)
0 (or not connected)
NODE 1
24VDC
0 (or not connected)
NODE 2
0 (or not connected)
24VDC
NODE 3
24VDC
24VDC