EasyManua.ls Logo

REFUSOL 20K-2T - Page 61

REFUSOL 20K-2T
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
REFUsol 20K-2T (853P020.200)
User manual
- 56 -
minutes, then turn ON the DC
switch. Check whether the fault is
rectified. If no, please contact
technical support.
ID08
IslandFault
Islanding faulty
ID09
GridOVPInstant1
Grid
instantaneous
voltage too high 1
ID10
GridOVPInstant2
Grid
instantaneous
voltage too high 2
ID11
VGridLineFault
Grid Line voltage
Faulty
ID12
InvOVP
Inverter
overvolatge
ID17
HwADFaultIGrid
The grid current
sampling error
ID18
HwADFaultDCI
The DCI sampling
error
ID19
HwADFaultVGrid
(DC)
Grid voltage
sampling faulty
DC side
ID20
HwADFaultVGrid
(AC)
Grid voltage
sampling faulty
AC side
ID21
GFCIDeviceFault(
DC)
Current leakage
samplingDC
side
There are internal faults of inverter,
turn OFF the DC switch, wait for 5
minutes, then turn ON the DC
switch. Check whether the fault is
rectified. If no, please contact
technical support.
ID22
GFCIDeviceFault(
AC)
Current leakage
samplingAC
side
ID23
HwADFaultIdcBr
anch
Current Branch
sampling faulty
ID24
HwADFaultIdc
DC input current
sampling faulty
ID29
ConsistentFault_
GFCI
The GFCI
sampling value
between the
master DSP and
salve DSP is not

Other manuals for REFUSOL 20K-2T

Related product manuals