REFUsol 20K-2T (853P020.200)
User manual
- 57 -
consistent
ID30
ConsistentFault_
Vgrid
The Grid voltage
sampling value
between the
master and
salve is not
consistent
ID31
ConsistentFault_
DCI
3 lines' DCI
consistency error
There are internal faults of inverter,
turn OFF the DC switch, wait for 5
minutes, then turn ON the DC
switch. Check whether the fault is
rectified. If no, please contact
technical support.
ID33
SpiCommFault(D
C)
SPI
Communication
Faulty DC side
ID34
SpiCommFault(A
C)
SPI
Communication
Faulty AC side
ID35
SChip_Fault
Chip FaultyDC
side
ID36
MChip_Fault
Chip FaultyAC
side))
ID37
HwAuxPowerFau
lt
Auxiliary power
fault
ID41
RelayFail
Relay faulty
Please check whether the resistance
to ground of PV string is too low and
whether the insulation of PV cable is
damaged. If the use method is not
ruled out, please contact the new
energy customer service of Capital
Airlines.
ID42
IsoFault
Low isolation
faulty
ID43
PEConnectFault
Ground faulty
ID44
PvConfigError
Input mode
incorrect
Please check the wiring of PV string,
whether each PV input is
independent. Check the setting of
MPPT input mode (Parallel mode /
independent mode) of the inverter
and correct them if applicable
ID45
CT Disconnect
CT Fault
Please check the wiring of input,

Other manuals for REFUSOL 20K-2T

Related product manuals