Parameter list
Parameter
Number
Description Default value Min Value Max Value
46 Display setting for the Setpoint mode
0 = Show the calculated setpoint (SP
calc
)
1 = Show the user defined setpoint adjustment
(SP
adj
)
1 0 1
47 Maximum setpoint increase
min = 0, max = 20
3 K 0 20
48 Maximum setpoint decrease
min = 0, max = 20
3 K 0 20
49 Brightness of segment at Active and Setpoint mode
as well as in the parameter list
70 % 0 100
50 Modbus address Factory set 1 254
51 Modbus Speed
0 = 4800 bps
1 = 9600 bps
2 = 19200 bps
3 = 38400 bps
1 0 3
52 Modbus parity and stop bit
0 = 8N2
1 = 8O1
2 = 8E1
3 = 8N1
2 0 3
53 Modbus Char timeout
Timeout should be at least 1.5 times a character, i.e.
at least 2 ms (@9 600 baud)
2 ms 2 1000
54 Modbus Answer delay 5 ms 5 1000
55 Version number Version dependent
- -
24 RCFD-230C manual, Rev. A