Heating capacity WLT 30 EC - WLT 50 EC
VS LV SD
Medium
nominal
Medium inlet
35 °C 40 °C 45 °C 50 °C 55 °C 60 °C 65 °C
Heating capacity
Mediu
m flow
rate
[m
3
/h]
Pres-
sure
loss
[kPa]
Q
H
[kW]
Q
H
[kW]
Q
H
[kW]
Q
H
[kW]
Q
H
[kW]
Q
H
[kW]
Q
H
[kW]
WLT 30
EC
1 150 18 0.230 13.0 0.57 0.76 0.95 1.22 1.40 1.50 1.66
2 360 33 0.323 13.0 1.24 1.67 2.08 2.67 3.06 3.27 3.64
3 450 39 0.370 15.6 1.43 1.91 2.39 3.07 3.51 3.76 4.18
4 510 43 0.397 17.0 1.61 2.16 2.70 3.46 3.96 4.24 4.72
5 560 45 0.480 23.1 1.77 2.37 2.96 3.80 4.35 4.66 5.18
WLT 40
EC
1 150 19 0.240 13.0 0.61 0.80 0.99 1.22 1.36 1.53 1.54
2 405 34 0.379 13.7 1.59 2.07 2.58 3.17 3.53 3.99 4.00
3 480 38 0.411 15.2 1.78 2.33 2.89 3.56 3.97 4.48 4.49
4 590 42 0.472 19.0 2.11 2.75 3.42 4.21 4.69 5.30 5.31
5 625 45 0.640 31.3 2.33 3.04 3.78 4.65 5.18 5.85 5.87
WLT 50
EC
1 150 18 0.250 19.5 0.60 0.80 0.99 1.23 1.38 1.56 1.74
2 570 32 0.611 19.5 2.20 2.93 3.65 4.51 5.05 5.72 6.36
3 470 40 0.689 23.5 2.58 3.44 4.28 5.29 5.92 6.71 7.47
4 910 46 0.763 27.3 2.86 3.81 4.75 5.87 6.57 7.44 8.28
5 950 47 0.830 31.0 3.13 4.17 5.19 6.42 7.19 8.14 9.06
Air inlet temperature TK 20 °C, 0% Glycol concentration, max. air flow
Q
H
= Heating capacity
, total
LV = Air flow [m
3
/h]
SD = Sound pressure level [dB(A)]
VS = Fan stage
REMKO WLT EC series
14