EasyManuals Logo

Resol DeltaSol BX User Manual

Resol DeltaSol BX
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
en
11
InstallationIndications, functions and optionsMessages Commissioning Operation and function
System 3: Solar system with 1 store and backup heating
The controller calculates the temperature difference between collector sensor
S1 and store sensor S2. If the difference is larger than or identical to the adjusted
switch-on temperature difference, the pump (R1) will be switched on and the store
will be loaded until the switch-off temperature difference or the maximum store
temperature is reached.
Backup heating (R4) can be carried out with a thermostat function (S3). If the
value at S3 reaches the switch-on temperature for the backup heating, the relay
is switched on. If the value exceeds the switch-off temperature for the backup
heating, the relay is switched off again.
R1
S2
S1
R4
S3
Te mp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PWM 1
PWM 2
N
R4
V40
VBus
GND
L'
VFS
RPS
Sensors
S1 Temperature collector 1 / GND
S2 Temperature store
base
2 / GND
S3 Temperature backup
heating
3 / GND
S4 Free 4 / GND
S5 Free 5 / GND
Relay
R1 Solar pump R1 / N / PE
R2 Free R2 / N / PE
R3 Free R3 / N / PE
R4 Backup heating / Store
loading pump
R4 / N / PE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Resol DeltaSol BX and is the answer not in the manual?

Resol DeltaSol BX Specifications

General IconGeneral
BrandResol
ModelDeltaSol BX
CategoryController
LanguageEnglish

Related product manuals