System 14: Solar system with store loading in layers and return preheating
The controller compares the temperature at sensor S1 to the temperatures at
sensors S2 and S3. If the measured temperature differences are higher than the
adjusted switch-on temperature differences, the pump (R1) will be activated and
the corresponding store zone will be loaded up to the adjusted store maximum
or set temperature respectively via the valve (R3). The priority logic effects prior
loading of the upper zone of the store.
With another temperature differential function (S5 heat source / S4 heat sink) re-
turn preheating (heating circuit backup) is possible via another valve (R2).
Sensors
S1 Temperature collector 1 / GND
S2 Temperature store
base
2 / GND
S3
Temperature store
top / Temperature
store return
preheating
3 / GND
S4 Temperature heating
return
4 / GND
S5 Free 5 / GND
Relay
R1 Solar pump R1 / N / PE
R2 Valve
return preheating
R2 / N / PE
R3 Solar valve R3 / N / PE
R4 Free R4 / N / PE
R3
R2
R1
S4
S2
S1
S3