System 16: 2-store solar system with valve logic and heat exchange control
The controller compares the temperature at sensor S1 to the temperatures at
sensors S2 and S4. If the measured temperature differences are higher than the
adjusted switch-on temperature differences, the pump (R1) will be activated and
the corresponding store will be loaded up to the adjusted store maximum or set
temperature respectively via the valve (R3). The priority logic effects prior loading
of store 1.
Heat exchange control to an existent store via an additional pump (R2) can be carried
out with another temperature differential function (S3 heat source / S4 heat sink)
.
Sensors
S1 Temperature collector 1 / GND
S2 Temperature store
base
2 / GND
S3 Temperature heat
exchange source
3 / GND
S4 Temperature store
2 base and heat
exchange sink
4 / GND
S5 Free 5 / GND
Relay
R1 Solar pump R1 / N / PE
R2 Store loading pump R2 / N / PE
R3 Solar valve R3 / N / PE
R4 Free R4 / N / PE
R2
R1
R3
S4
S3
S2
S1