D e lt a S o l
®
E
© RESOL 10306_DeltaSol_E.monus.indd
| 32
The relay allocated to the function block is switched on
when the adjusted switch-on temperature (Th(x)on) is
reached. It is switched off when the adjusted switch-off
temperature (Th(x)off) is reached. The switching conditions
of all other activated functions of the function block have
to be fulfilled as well.
Î Allocate the reference sensor in the expert menu.
Î Adjust the maximum temperature limitation with
Th(x)off > Th(x)on and the minimum tempera-
ture limitation with Th(x)on > Th(x)off.
The temperatures cannot be set to an identical value.
Thermostat function
(Function block 1 ... 5):
Arrangement/Options/Thermo1 (...10)
selection: “Yes”, “No”
factory setting: “No“
Arrangement/adj. values/Th1(...10)on
adjustment range: - 40.0 ... 480.0 °F
factory setting: 120.0 °F
Arrangement/adj. values/Th1(...10)off
adjustment range: - 40.0 ... 480.0 °F
factory setting: 120.0 °F
Arrangement/Expert/Sen-Th1 (...10)
adjustment range: 1 ... 10
factory setting: 3 (...10)
The relay allocated to the function block is switched on as
soon as the adjusted switch-on temperature (DTh(x)on) is
reached. It is switched off as soon as the adjusted switch-off
temperature (DTh(x)off) is reached. The switching condi-
tions of all other activated functions of the function block
have to be fulfilled as well.
DT-function (function block 1 ... 5):
Arrangement/Options/DT-func 5 (...9)
selection: “Yes”, “No”
factory setting: “No”
Arrangement/adj. values/DT5(...9)on
adjustment range: 2.0 ... 100.0 °Ra
factory setting: 10.0 °Ra
Arrangement/adj. values/DT5(...9)off
adjustment range: 1.0 ... 99.0 °Ra
factory setting: 6.0 °Ra
Arrangement/Expert/Sen 1-DT5(...9)
adjustment range: 1 ... 10
factory setting: 3 (...10)
Arrangement/Expert/Sen 2-DT5(...9)
adjustment range: 1 ... 10
factory setting: 4 (...10)
Each timer function provides up to 21 time frames (3 for
each day). The relay allocated to the function block is acti-
vated as long as the time frame (t(x)on ... t(x)off) is open.
The switching conditions of all other activated functions of
the function block have to be fulfilled as well.
Timer function (function block 1 ... 5):
Arrangement/Options/timer 1 (...5)
selection: “Yes”, “No”
factory setting: “No”
Arrangement/adj. values/timer 1 (...5)/t1(...21)-on
adjustment range: 00:00 ... 00:00
factory setting: 22:00
Arrangement/adj. values/timer 1 (...5)/t1(...21)-
off
adjustment range: 00:00 ... 00:00
factory setting: 05:00
Î Adjust the reference sensor in the expert menu.