D e lt a S o l
®
E
© RESOL 10306_DeltaSol_E.monus.indd
37 |
Up to 3 additional external heating circuit modules (HKM)
can be activated if further compensated heating circuits are
required. The HKM module is optional and is not included
in the full kit.
Heating circuit module
Arrangement/Heat. circuit/Options/Hc1(2,3)Module
selection: “Yes”, “No”
factory setting: “No”
Arrangement/Heat. circuit/hc/Expert/Sen. out-
door
adjustment range: 1 ... 17
factory setting: 7
change to: 13
The displays and functions are comparable to those of the
internal heating circuit (see also manual “RESOL HKM 2”).
Arrangement/heat. circuit/Hc-Module/...
External heating module:
If the external heating circuit module HKM2 is additionally
used, only 1 outdoor temperature sensor is required.
In order to ensure that all heating circuits control using the
same outdoor temperature, adjust to sensor 13 and connect
the external sensor to the HKM module.
This function switches off the heating circuit when domestic
hot water is given priority.
For this purpose, the option domestic hot water priority
and backup heating via tank loading (see 4.2) of the control-
ler D e lt a S o l
®
E have to be active as well.
Tank priority:
Arrangement/heat. circuit/hc1(2,3)module/tank
prio.
selection: “On”, “Off
factory setting: “Off
4.3 Menu: Energy metering
WMZ/Options/WMZ (WMZ-Module)
selection: “Yes”, “No”
factory setting: “No”
WMZ/WMZ 1/ Expert/flowmeter
selection: “Yes”, “No”
factory setting: “No”
WMZ/WMZ 1/Expert/Sen. flow
adjustment range: 1 ... 10
factory setting: 9
WMZ/WMZ 1/Expert/Sen. return
adjustment range: 1 ... 10
factory setting: 10
The controller has a separate integrated calorimeter
which can be configured with or without flowmeter V40.
Furthermore, the values of a separate WMZ module can
be displayed.
Î Allocate the sensors.
Factory settings are as shown – but other sensors can be
allocated without influencing their orginal function in the
system.
The heat quantity measurement calculation (estimation)
uses the difference between flow and return temperature
and the user entered flow rate. The flow rate should be read
from the window of the flow setter at 100 % pump speed.
Heat quantity measurement is carried out when the output
selected in the
relay” menu is active.
Heat quantity estimation without flowmeter
RESOL V40
Set
WMZ/Options/WMZ to “Yes” and
WMZ/WMZ 1/Expert/flowmeter to “No”
WMZ/WMZ1/Expert/flow
adjustment range: 1.0 ... 50.0 l
factory setting: 3.0 l
WMZ/WMZ 1/Expert/Relay
adjustment range: 1 ... 7
factory setting: 1

Other manuals for Resol DeltaSol E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Resol DeltaSol E and is the answer not in the manual?

Resol DeltaSol E Specifications

General IconGeneral
BrandResol
ModelDeltaSol E
CategoryController
LanguageEnglish

Related product manuals