1.3 Installation Conditions
Depending on rating, the frequency converters are available in different sizes. In
order not to affect device cooling, the frequency converter must always be in-
stalled upright. For perfect heat dissipation, the minimum installation spacing to
the devices shown in the drawing must be observed.
Fig. 1-1: Installation conditions
● The frequency converter shown above is Frame 1. The minimum
installation spacing stated applies to Frame 1 to Frame 7.
● The frequency converter must be vertically installed.
● If one frequency converter is arranged above another, make sure
the upper limit of air temperature into the inlet is not exceeded
(see chapter 1.2 "Ambient Conditions" on page 1). A baffle plate
is recommended between the frequency converters to prevent the
rising hot air being drawn into the upper frequency converter if
the upper limit of air temperature is exceeded.